The HJ-DYZ-600 intelligent high-frequency switch-mode power system comprises a cabinet, AC distribution, rectifier modules (up to 12 fully configured), a monitoring module, and DC distribution. It offers comprehensive battery management-including low-voltage protection and optional load disconnect-plus temperature compensation, automatic voltage regulation, stepless current limiting, capacity calculation, online battery testing, and sleep energy-saving. Networked design with RS232/RS485 and dry-contact ports enables flexible networking, remote monitoring, and unattended operation, with full AC/DC surge protection and complete fault protection/alarm functions.
Bericht verzenden krijg Prijs
| Environmental parameters | Bedrijfsomstandigheden | Transportvoorwaarden | Opslag condities | geldende normen | Opmerkingen | |||
| Categorie | Parameter | Eenheid | ||||||
| Klimaat omstandigheden | Temperatuur | Lage temperatuur | ℃ | -33 | -40 | -40 | YD/T 1058-2000 Clausules 4.1.1 en 4.1.2 | Start bij vollast bij −40℃; lineaire vermogensreductie van 20% van +55 tot +65℃. |
| Hoge temperatuur | ℃ | 65 | 70 | 70 | ||||
| Temperatuurverandering | ℃/min | / | 1 | / | ETS 300 019-2-2 T2.3 | |||
| Omgevingstemperatuur | ℃ | -33-65 | Extreme bedrijfstemperatuur bij volledige belasting | |||||
| Bewaar temperatuur | ℃ | -40-70 | ||||||
| Vochtigheid | Relatieve vochtigheid | % | 5-90 | 90 (40±2℃) | / | YD/T 1058-2000 Clausule 4.1.3 | Short-term test: 0-95%, max 95%, non-condensing | |
| condensatie | Ja / Nee | Nee | Nee | Ja | ||||
| Luchtdruk | Lage druk | kPa | 86 | 70 | 70 | YD/T 1058-2000 Clausule 4.1.4 | Module testen alleen | |
| Hoge druk | kPa | 106 | 106 | 106 | ||||
| Hoogte | m | ≤ 4000 | Boven 2000 m, verlaag de temperatuur met 0.5℃ per extra 100 m. | |||||
Opmerking: Specificaties kunnen zonder voorafgaande kennisgeving worden gewijzigd in verband met productverbeteringen. Datasheet
Fully digital interleaved PFC innovative control with limited bipolar ZVS full-bridge topology, current-doubler rectifier topology, and dual MCUs for fully digital monitoring
Rectifiers use PFC so AC input current matches the voltage waveform and phase; high system efficiency saves energy and reduces OPEX
High-frequency PWM conversion reduces switching losses and EMI, allowing installation inside switching equipment rooms
Intelligent battery management with continuously settable equalization/float voltages and charge current limits via controller or remote system; supports float, equalization, and battery testing
Equipotential design across the cabinet improves EMC and lightning protection
Het is geschikt voor verschillende energieverbruikscenario's, zoals woongebouwen en commerciële kantoorgebouwen.
Wij streven ernaar om u snel en professioneel te ondersteunen, zodat wij altijd aan uw energiebehoeften voldoen met de hoogst mogelijke service.
Wij zijn er om uw vragen te beantwoorden en u de energieoplossingen te bieden die het beste bij uw behoeften passen.